When analyzing a single line-to-ground fault from phase A to ground at a three-phase bus, it is important to consider the fault impedance. This impedance is zero for a bolted fault, equal to the arc impedance for an arcing fault, and represents the total fault impedance for a transmission-line insulator flashover. To derive sequence and phase currents, fault conditions are translated from the phase domain to the sequence domain.

For line-to-line faults occurring between phases B and C, the conditions in the phase domain are similarly converted to the sequence domain. This conversion establishes the relationship between phase and sequence currents. In these fault conditions, the positive-sequence and negative-sequence networks are connected in parallel at the fault terminals through the fault impedance, ensuring the accurate representation of the fault.

In the case of a double line-to-ground fault, which occurs from phase B to phase C via fault impedance to ground, fault conditions must first be determined in the phase domain. These conditions are then transformed to the sequence domain. This process involves connecting the zero-sequence, positive-sequence, and negative-sequence networks in parallel at the fault terminal. By doing so, the sequence fault currents and line-to-ground voltages can be accurately determined.

This approach to fault analysis, by translating conditions between the phase and sequence domains, allows for the comprehensive evaluation of fault currents and voltages. It ensures that all relevant network connections and fault impedances are appropriately considered, providing a detailed understanding of the fault's impact on the system.

Из главы 29:

article

Now Playing

29.8 : Fault Types

Symmetrical and Unsymmetrical Faults

37 Просмотры

article

29.1 : Переходные процессы цепи серии R—L

Symmetrical and Unsymmetrical Faults

46 Просмотры

article

29.2 : Трехфазное короткое замыкание — разгруженная синхронная машина

Symmetrical and Unsymmetrical Faults

50 Просмотры

article

29.3 : Трехфазные системы короткого замыкания

Symmetrical and Unsymmetrical Faults

34 Просмотры

article

29.4 : Матрица импеданса шины

Symmetrical and Unsymmetrical Faults

48 Просмотры

article

29.5 : Выбор автоматического выключателя и предохранителя

Symmetrical and Unsymmetrical Faults

47 Просмотры

article

29.6 : Секвенсионные сети вращающихся машин

Symmetrical and Unsymmetrical Faults

55 Просмотры

article

29.7 : Модели последовательности для каждой единицы измерения

Symmetrical and Unsymmetrical Faults

49 Просмотры

JoVE Logo

Исследования

Образование

О JoVE

Авторские права © 2025 MyJoVE Corporation. Все права защищены