An ideal Y-Y transformer, grounded through neutral impedances, displays per-unit sequence networks akin to those of a single-phase ideal transformer when subjected to balanced positive- or negative-sequence currents. These currents do not produce neutral currents, and their associated voltage drops.

Zero-sequence currents, which are identical in magnitude and phase, generate a neutral current, resulting in voltage drops across the neutral impedance and the low-voltage winding. If the transformer's neutral is ungrounded, zero-sequence currents cannot flow to the ground but can still circulate within the windings.

Practical Y-Y transformers' per-unit sequence networks incorporate external impedances. Their shunt branches represent a balanced-Y impedance load, with each phase corresponding to a core loss resistor parallel to the magnetizing inductance. These transformers possess identical per-unit positive- and negative-sequence impedances, whereas the neutral impedances influence the zero-sequence network.

Delta-delta transformers feature per-unit sequence networks with identical positive- and negative-sequence impedances. However, different winding connections can influence these impedances in practical transformers. Per-unit sequence models of three-phase, three-winding transformers can be constructed by connecting three identical single-phase transformers, using a common S-base for terminals and proportional voltage bases.

In the general zero-sequence network, the configuration of the high-voltage windings dictates the high-voltage connection. Per-unit negative-sequence network impedances always match the positive-sequence network impedances.

From Chapter 29:

article

Now Playing

29.7 : Per-Unit Sequence Models

Symmetrical and Unsymmetrical Faults

38 Views

article

29.1 : Series R—L Circuit Transients

Symmetrical and Unsymmetrical Faults

28 Views

article

29.2 : Three-Phase Short Circuit—Unloaded Synchronous Machine

Symmetrical and Unsymmetrical Faults

35 Views

article

29.3 : Power System Three-Phase Short Circuits

Symmetrical and Unsymmetrical Faults

24 Views

article

29.4 : Bus Impedance Matrix

Symmetrical and Unsymmetrical Faults

36 Views

article

29.5 : Circuit Breaker and Fuse Selection

Symmetrical and Unsymmetrical Faults

26 Views

article

29.6 : Sequence Networks of Rotating Machines

Symmetrical and Unsymmetrical Faults

40 Views

article

29.8 : Fault Types

Symmetrical and Unsymmetrical Faults

26 Views

JoVE Logo

Privacy

Terms of Use

Policies

Research

Education

ABOUT JoVE

Copyright © 2025 MyJoVE Corporation. All rights reserved