Understanding the inductance of transmission lines is crucial for efficient design and operation in electrical power systems. This discussion delves into the inductance characteristics of single-phase two-wire and three-phase three-wire transmission lines with equal phase spacing.

Single-Phase Two-Wire Line:

A single-phase line consists of two solid cylindrical conductors, denoted as x and y. Each conductor carries phasor currents ix and iy, respectively. Given that the sum of these currents is zero, we can calculate the total flux linking conductor x. This flux linkage is given by:

Equation1

Where rx' is the effective radius of conductor x, accounting for the proximity effect.

The inductance per conductor, Lx of conductor x, is then:

Equation2

Similarly, for conductor y, the flux linkage and inductance are computed. The total inductance of the single-phase circuit, also known as loop inductance, is:

Equation3

Three-Phase Three-Wire Line:

For a three-phase line, there are three solid cylindrical conductors, a, b, and c, each with equal radius r and equal phase spacing D. Assuming balanced positive-sequence currents, the total flux linking phase a is:

Equation4

From this, the inductance of phase a is derived:

Equation5

Due to symmetry, the same inductance applies to phases b and c. For a balanced three-phase operation, only one phase needs consideration since each phase's flux linkages are equal in magnitude and displaced by 120 degrees.

Understanding these inductance calculations helps in the design and analysis of transmission lines, ensuring minimal losses and optimal performance.

Del capítulo 27:

article

Now Playing

27.4 : Inductance: Single-Phase And Three-Phase Line

Transmission Line Parameters

88 Vistas

article

27.1 : Consideraciones sobre el diseño de la línea de transmisión

Transmission Line Parameters

74 Vistas

article

27.2 : Resistencia y conductancia

Transmission Line Parameters

46 Vistas

article

27.3 : Inductancia: conductor cilíndrico sólido

Transmission Line Parameters

112 Vistas

article

27.5 : Impedancias en serie: línea trifásica

Transmission Line Parameters

53 Vistas

article

27.6 : Capacitancia: Línea monofásica y trifásica

Transmission Line Parameters

88 Vistas

article

27.7 : Entradas de derivación

Transmission Line Parameters

70 Vistas

JoVE Logo

Privacidad

Condiciones de uso

Políticas

Investigación

Educación

ACERCA DE JoVE

Copyright © 2025 MyJoVE Corporation. Todos los derechos reservados