Understanding the inductance of transmission lines is crucial for efficient design and operation in electrical power systems. This discussion delves into the inductance characteristics of single-phase two-wire and three-phase three-wire transmission lines with equal phase spacing.

Single-Phase Two-Wire Line:

A single-phase line consists of two solid cylindrical conductors, denoted as x and y. Each conductor carries phasor currents ix and iy, respectively. Given that the sum of these currents is zero, we can calculate the total flux linking conductor x. This flux linkage is given by:

Equation1

Where rx' is the effective radius of conductor x, accounting for the proximity effect.

The inductance per conductor, Lx of conductor x, is then:

Equation2

Similarly, for conductor y, the flux linkage and inductance are computed. The total inductance of the single-phase circuit, also known as loop inductance, is:

Equation3

Three-Phase Three-Wire Line:

For a three-phase line, there are three solid cylindrical conductors, a, b, and c, each with equal radius r and equal phase spacing D. Assuming balanced positive-sequence currents, the total flux linking phase a is:

Equation4

From this, the inductance of phase a is derived:

Equation5

Due to symmetry, the same inductance applies to phases b and c. For a balanced three-phase operation, only one phase needs consideration since each phase's flux linkages are equal in magnitude and displaced by 120 degrees.

Understanding these inductance calculations helps in the design and analysis of transmission lines, ensuring minimal losses and optimal performance.

Dal capitolo 27:

article

Now Playing

27.4 : Inductance: Single-Phase And Three-Phase Line

Transmission Line Parameters

113 Visualizzazioni

article

27.1 : Transmission Line Design Considerations

Transmission Line Parameters

96 Visualizzazioni

article

27.2 : Resistance and Conductance

Transmission Line Parameters

54 Visualizzazioni

article

27.3 : Inductance: Solid Cylindrical Conductor

Transmission Line Parameters

137 Visualizzazioni

article

27.5 : Series Impedances: Three-Phase Line

Transmission Line Parameters

75 Visualizzazioni

article

27.6 : Capacitance: Single-Phase And Three-Phase Line

Transmission Line Parameters

107 Visualizzazioni

article

27.7 : Shunt Admittances

Transmission Line Parameters

81 Visualizzazioni

JoVE Logo

Riservatezza

Condizioni di utilizzo

Politiche

Ricerca

Didattica

CHI SIAMO

Copyright © 2025 MyJoVE Corporation. Tutti i diritti riservati